3.4

M+FX5CCLIEF_Recv

Name
M+FX5CCLIEF_Recv
Overview
Item
Description
Overview
Reads the data received from the programmable controller of another station.
Symbol
(1)
(2)
(3)
Labels
■Input label
No.
Variable name
Name
(1)
i_bEN
Execution command
(2)
i_stModule
Module label
(3)
i_uRecvChannel
Receive data storage
channel
■Output label
No.
Variable name
Name
(4)
o_bENO
Execution status
(5)
o_bOK
Normal completion
(6)
o_bErr
Error completion
(7)
o_uErrId
Error code
(8)
o_uRecvDataLength
Receive data length
(9)
o_uRecvData
Receive data storage
device
M+FX5CCLIEF_Recv
B
:
i_bEN
DUT
:
i_stModule
UW
:
i_uRecvChannel
o_uRecvDataLength
o_uRecvData
(10) pbi_bReadTiming
(11) pbi_uMonitorTime
(12) pbo_uResendCount
(13) pbo_u4ErrTime
(14) pbo_uErrNetworkNo
(15) pbo_uErrStationNo
(16) pbo_uSendNetworkNo
(17) pbo_uSendStationNo
(18) pbo_uSendChannel
Data type
Bit
Structure
Word [unsigned]
Data type
Bit
Bit
Bit
Word [unsigned]
Word [unsigned]
Word [unsigned]
o_bENO
:
B
(4)
o_bOK
:
B
(5)
o_bErr
:
B
(6)
o_uErrId
:
UW
(7)
:
UW
(8)
:
UW
(9)
Range
Description
ON, OFF
ON: The FB is activated.
OFF: The FB is not activated.
The setting range
Specify the module label of the FX5-CCLIEF.
differs depending on
the module label.
1, 2
Specify the channel containing the data to be read.
Default value
Description
OFF
ON: The execution command is ON.
OFF: The execution command is OFF.
OFF
When this label is ON, it indicates that reading of the
received data has completed normally.
OFF
When this label is ON, it indicates that an error has
occurred in the FB.
0
Stores the error code that occurred in the FB.
0
The number of received data is stored.
1 to 960 words
0
Specify the start number of the device for storing
received data.
3 CC-LINK IE FIELD NETWORK MODULE FB
3.4 M+FX5CCLIEF_Recv
3