Mitsubishi Electric MELSEC iQ-F Reference page 36

Fx5 ethernet/cc-link ie function block
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

No.
Variable name
(7)
i_uDataLength
(8)
i_uSendData
■Output label
No.
Variable name
(9)
o_bENO
(10)
o_bOK
(11)
o_bErr
(12)
o_uErrId
■Public label
No.
Variable name
(13)
pbi_uTargetStation
(14)
pbi_bArrivalConfirm
(15)
pbi_uResendCountM
ax
3 CC-LINK IE FIELD NETWORK MODULE FB
34
3.3 M+FX5CCLIEF_Send
Name
Data type
Send data length
Word [unsigned]
Send data storage
Word [unsigned]
device
Name
Data type
Execution status
Bit
Normal completion
Bit
Error completion
Bit
Error code
Word [unsigned]
Name
Data type
Target station
Word [unsigned]
specification method
Arrival
Bit
acknowledgment
Maximum number of
Word [unsigned]
resends
Range
Description
1 to 960
Specify the number of words to be sent.
• When reading data from RCPU, QCPU, LCPU, or
FX5CPU: 1 to 960
• When reading data from QnACPU: 1 to 480
Specify the head device of own station containing the
send data.
Default value
Description
OFF
ON: The execution command is ON.
OFF: The execution command is OFF.
OFF
When this label is ON, it indicates that the data has been
sent correctly.
OFF
When this label is ON, it indicates that an error has
occurred in the FB.
0
Stores the error code that occurred in the FB.
Range
Description
0 to 2
Specify the target station specification method.
• 0: Station number specification → Station with the
station number specified in "Target station number"
• 1: Group specification → All stations with the transient
transmission group number specified with "target
station number"
• 2: All stations → All stations with the network number
specified with "target station network number"
(Broadcast simultaneously to all stations excluding
own station)
Group specification cannot be used when the target
group is the CC-Link IE Field network.
Group specification and All station specification can be
specified only when "Arrival acknowledgment" = OFF
(None).
ON, OFF
Specify whether to use arrival acknowledgment.
■OFF: None
• When the target station is within the own network,
sending data from the own station completes the
sending.
Execution
source
• When the target station is within another network,
data arrival to the relay station within the own network
completes the sending.
Execution
source
■ON: Check
• Sending data is completed when the data is written to
the target station.
Completed
Target
station
0 to 15
Specify the number of resends to be performed if the
data transfer is not completed within the monitoring time
specified by "arrival monitoring time".
• 0 to 15
Completed
Target
station
Completed
Relay
Target
station
station
Execution
Relay
source
station
Completed
Target
station