Cpu module, built-in ethernet function
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

password-lock
[Function]
[Specification format]
[Example]
*3
Use this command only when FTP communication port is specified as a remote password check target.
run
[Function]
[Specification format]
[Example 1]
[Example 2]
[Example 3]
[Note]
status
[Function]
[Specification format]
102
Locks the remote password set in the CPU module.
quote password-lock
The following is displayed as an execution result upon completion.
200 Command Okey
When locking the remote password:
quote password-lock
Changes the CPU module state to RUN. (Remote RUN.)
At this time, device memory clear can be specified.
quote run [mode [clear mode]]
• Mode: Specify whether to force remote RUN or not.
0: Normal RUN (default)
1: Forced RUN
• Clear mode:
Specify the CPU module device memory clear (initialization) processing performed when
the operation starts by executing remote RUN.
0 : Do not clear device (default)
1 : Clear other than the latch range
2 : Clear all including the latch range
The following message is displayed as an execution result upon completion.
200 Command successful
When executing remote RUN, with "Normal RUN" and "Do not clear device" specified:
quote run
When executing remote RUN, with "Forced RUN" and "Do not clear device" specified:
quote run 1
When executing remote RUN, with "Forced RUN" and "Clear other than the latch range":
specified
quote run 1 1
• Forced RUN should be used only to force remote RUN to the CPU module from another
device when a device that executed remote STOP to the CPU module have a problem
and cannot perform remote RUN.
With Normal RUN, the CPU module state cannot be changed from STOP/PAUSE to RUN
if the previous state is set by a different device.
• Specify the clear mode at the start of an operation, according to the system arrangement.
After completing the specified clear processing, the CPU module runs in accordance with
the PLC parameter settings ("Initial Device value" setting on the PLC file tab).
Displays information of the CPU module operation.
This command is used to check the information on the CPU module operation before
transferring a file to the CPU module.
quote status
One of the following is displayed as an execution result upon completion.
• When the CPU module is in RUN state: "RUN"
• When the CPU module is in STOP state: "STOP"
• When the CPU module is in PAUSE state: "PAUSE"
*3