Mounting The Shield Plate For Pt Power Modules; Additional Components - Siemens SINAMICS PM240-2 Hardware Installation Manual

Power module for sinamics g120
Hide thumbs Also See for SINAMICS PM240-2:
Table of Contents

Advertisement

Table 4- 5
Frame
size
FSA
FSB
FSC
The Power Modules are designed for mounting without any lateral cooling air clearance. For toler-
1)
ance reasons, we recommend a lateral clearance of 1 mm.
4.4.5

Mounting the shield plate for PT Power Modules

The shield plates and fixings screws are included in the inverter accessory kit.
Figure 4-5
4.5

Additional components

Depending on the particular application, additional components may be required for your
system. Information about additional components is provided in the following Sections:
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
Drilling dimensions, cooling clearances and fixing
Control cabinet cutout [mm]
a
b
c
103
106
27
148
134
34.5
123
174
30.5
Mounting the shield plate
Connection overview (Page 49)
Accessories (Page 105).
Cooling air clearances
[mm]
d
e
Top
Bottom
198
88
80
304
116
80
365
156
80
Installing/mounting
4.5 Additional components
Fixing/torque
1)
Front
100
100
8 x M5 / 3.5 Nm
100
100
8 x M5 / 3.5 Nm
100
100
10 x M5 / 3.5 Nm
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents