Installing/Mounting; Installation Conditions - Siemens SINAMICS PM240-2 Hardware Installation Manual

Power module for sinamics g120
Hide thumbs Also See for SINAMICS PM240-2:
Table of Contents

Advertisement

Installing/mounting

4.1

Installation conditions

General installation conditions
When installing the Power Modules carefully observe the conditions listed below in order to
guarantee reliable, continuous and disturbance-free operation.
● The Power Modules are designed for installation in a control cabinet.
● The Power Modules are certified for use in environments with degree of pollution 2
without condensation; i.e. in environments where no conductive pollution/dirt occurs.
● The built-in units fulfill IP20 degree of protection.
● Devices with push-through technology (PT devices) have IP20 degree of protection,
at the rear of the control cabinet, IP55.
● You can find the permissible conductor cross-sections for the terminals in:
● The following section describes how you can install the Power Modules in compliance
with EMC regulations:
Inverters for systems in the United States / Canada (UL/cUL)
● For a system configuration in conformance with UL/cUL, use the fuse types approved for
UL/cUL, specified in the Technical data, or the circuit breakers under the following
Internet address.
● The integrated semiconductor short-circuit protection does not provide cable protection.
● On the system side, provide cable protection in conformance with NEC or CEC, Part 1
and the local regulations.
● The inverters provide internal motor protection corresponding to UL61800-5-1. The
protection threshold is 115 % of the inverter full load current. When commissioning, you
can adapt the motor overload protection using parameter p0640.
● For frame size FSF, to connect the line supply and motor only use UL approved ring-type
cable lugs (ZMVV), which are certified for the particular voltage, with a permissible
current of at least 125 % of the input and output current. Use the higher value as basis.
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
Connection terminals at the inverter (Page 53)
EMC-compliant installation of a machine or system (Page 23)
Fuse types: Technical data (Page 65)
Circuit breaker
(https://support.industry.siemens.com/cs/ww/en/view/109486009)
4
21