3 - If the CNI2 is programmed to call more than one computer, and the computers'
clocks are different by more than 20 seconds, this will result in Clock Resync alarms.
4 - During packet (Internet) connections DC-2009 prepares the message containing the
new time-of-day and sends it to the CNI2. If a packet does not arrive after a certain
amount of time, the same packet is retransmitted. This will be repeated several more
times before the connection is terminated. If it takes over 20 seconds to deliver the
packet, then the time in the message will be 20 seconds older than the CNI2's current
time.

Remote Daily Volume Low Input-1,2,3,4

These alarms occur if the daily volume use is below the limits for pulse inputs 1, 2, 3 and 4,
respectively.

Remote Daily Volume High Input-1,2,3,4

These alarms occur if the daily volume use is above the limits for pulse inputs 1, 2, 3 and 4,
respectively.

Remote TTI Consumption Low Input-1,2,3,4

These alarms occur if the interval volume use is below the limits for pulse inputs 1, 2, 3 and 4,
respectively.

Remote TTI Consumption High Input-1,2,3,4

These alarms occur if the interval volume use is above the limits for pulse inputs 1, 2, 3 and 4,
respectively.

Low Battery Alarm

This alarm indicates that the battery pack in the CNI2 needs to be replaced as soon as possible.
The voltage level at which the alarm will occur is programmed using MP32. The battery should
be changed as soon as possible to continue uninterrupted service.
Note About Batteries
Battery voltage level drops in cold weather. If the unit is located in cold climates you may
receive occasional low-battery alarms as the temperature drops. As the unit warms up during
the day the voltage may return to acceptable levels. However, any low-battery alarm should be
taken seriously and the battery should be replaced soon. If the battery gets too low the unit may
no longer be able to make calls and may not be able to save its' pulse data.