Figure 5-7 Lcd Screen (Mms Operation) - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Transfer from Maintenance Bypass to MMS Bypass Operation
1.
Close the TTC System Output Circuit Breaker 52L.
2.
Open the TTC Circuit Breaker 52-MB.
NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start operation can only be performed remotely. If local inverter start operation is
required (at the UPS), select "LOCAL ONLY" or "REMOTE & LOCAL" in the
OPERATION MENU.
Transfer from UPS MMS Bypass Operation to UPS MMS Inverter Operation
1.
Transfer MMS Bypass Operation to MMS Inverter Operation from Operation Menu on any UPS LCD as
shown in Fig. 3.6.
Transfer from UPS MMS Inverter Operation to UPS MMS Bypass Operation
1.
Transfer MMS Inverter Operation to MMS Bypass Operation from Operation Menu on any UPS LCD as
shown in Fig. 3.6.
*Meaning of the icons in Figure 3.6
START: MMS Inverter Operation
STOP: MMS Bypass Operation
G9000 Installation and Operation Manual – 61480-012

Figure 5-7 LCD Screen (MMS Operation)