2
OVERVIEW
TOSHIBA G9000 Uninterruptible Power Supply Systems (UPS) need a TOSHIBA SYNC KIT whenever two SMS UPSs
are installed in a synchronous operation configuration.
Each TOSHIBA SYNC KIT contains all hardware necessary for one pair of master and slave UPS to operate in a
synchronous configuration. Each additional UPS unit will require another sync kit, if applicable. This manual contains kit
installation and startup information specifically for 1000kVA capacity models of the G9000 Series UPS.
The UPS requires de-energized condition when the TOSHIBA Sync KIT is installed and the
parallel-connection works are carried out for safety.
CAUTION
BYPASS Input
AC Input
BYPASS Input
AC Input
G9000 Series 1000kVA TOSHIBA SYNC KIT Installation Manual – 94471-001
UPS #A: MASTER G9000
CONV
INV
UPS #B: SLAVE G9000
CONV
INV
IOAU-19*
TN13
29 30
Jumper
Figure 2-1 Synchronous Operation Configuration
TOSHIBA Sync circuit
Master
Qty. 3 #16AWG, 600V insulation,
multi-strand, twisted trio wire, with ring lugs
Field installed by Others
VSAU-48*
TOSHIBA Sync circuit
* – PCB revision suffix may be applied.
for #12 screws.
To Load
STS
PDU
Slave
3