Parameter List
Parameter
73
Analog input selection
Terminal 1 added
compensation amount
242
(terminal 2)
Terminal 1 added
compensation amount
243
(terminal 4)
Override bias
252
Override gain
253
Terminal 4 input selection
267
74
Input filter time constant
Speed setting filter 1
822
Torque setting filter 1
826
Speed setting filter 2
832
Torque setting filter 2
836
Analog input offset
849
adjustment
Reset selection/
75
disconnected PU detection/
PU stop selection
76
Fault code output selection
77
Parameter write selection
Reverse rotation prevention
78
selection
114
Incre
Name
ments
1
0.1%
0.1%
0.1%
0.1%
1
1
0.001s
0.001s
0.001s
0.001s
0.1%
1
1
1
1
Initial
Range
Value
You can select the input specifications of terminal 2
(0 to 5V, 0 to 10V, 0 to 20mA) and input specifications
of terminal 1 (0 to ±5V, 0 to ±10V).
To change the terminal 2 to the voltage input
0 to 7,
1
specification (0 to 5V/ 0 to 10V), turn OFF (initial
10 to 17
status) the voltage/current input switch 2. To change
it to the current input (0 to 20mA), turn ON the
voltage/current input switch 2.
Override and reversible operation can be selected.
Set the ratio of added compensation amount when
100%
0 to 100%
terminal 2 is the main speed.
Set the ratio of added compensation amount when
75%
0 to 100%
terminal 4 is the main speed.
Set the bias side compensation value of override
50%
0 to 200%
function.
Set the gain side compensation value of override
150%
0 to 200%
function.
Terminal 4 input
0
4 to 20mA
0
Terminal 4 input
1
0 to 5V
Terminal 4 input
2
0 to 10V
The primary delay filter time constant for the analog
1
0 to 8
input can be set.
A larger setting results slower response.
Set the time constant of the primary delay filter
0 to 5s,
9999
relative to the external speed command (analog input
9999
command).
Set the time constant of the primary delay filter
0 to 5s,
9999
relative to the external torque command (analog
9999
input command).
0 to 5s,
Second function of Pr. 822 (valid when the RT
9999
9999
terminal is on)
0 to 5s,
Second function of Pr. 826 (valid when the RT
9999
9999
terminal is on)
This function provides speed command by analog
input (terminal 2) with offset and avoids frequency
100%
0 to 200%
command to be given due to noise under 0 speed
command.
You can select the reset input acceptance, disconnected
PU (FR-DU07
0 to 3,
detection function and PU stop function.
14
14 to 17
For the initial value, reset always enabled, without
disconnected PU detection, and with PU stop
function are set.
0
Without fault code output
0
1
With fault code output
2
Fault code output at fault occurrence only
0
Write is enabled only during a stop
1
Parameter write is disabled.
0
Parameter write is enabled in any operation mode
2
regardless of operating status.
0
Both forward and reverse rotations allowed
0
1
Reverse rotation disallowed
2
Forward rotation disallowed
Description
Turn ON the voltage/
current input switch
1(initial status).
Turn OFF the voltage/
current input switch 1.
/FR-PU07
/FR-PU04) connector