Siemens SIMATIC ET 200SP Manual page 86

Technology module tm posinput 1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record
Bit →
Bit 7
Byte ↓
16
16
Reserved
Edge selection (DI0):
2)
00
01
10
11
17
18
19
Frequency:
Count direction for syn-
chronization
0
: Once
00
B
1
: Periodi-
01
B
cally
10
11
86
Bit 6
Bit 5
: Invalid
B
: At rising edge
B
: At falling edge
B
: Invalid
B
: Invalid
B
: Up
B
: Down
B
: In both directions
B
Bit 4
Bit 3
Behavior of DI0
Select level
Reserved
2)
(DI0):
0
: Active
B
with high
level
1
: Active
B
with low
level
Behavior of DI1:
See Byte 16
Reserved
2)
Reserved
Input delay:
2)
0000
: None
B
0001
: 0.05 ms
B
0010
: 0.1 ms
B
0011
: 0.4 ms
B
0100
: 0.8 ms
B
0101
: 1.6 ms
B
0110
: 3.2 ms
B
0111
: 12.8 ms
B
1000
: 20 ms
B
1001 to 1111
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Bit 2
Bit 1
Set function of DI (DI0):
000
: Gate start/stop (level-triggered)
B
001
: Gate start (edge-triggered)
B
010
: Gate stop (edge-triggered)
B
011
: Synchronization
3)
B
100
: Enable synchronization at sig-
B
nal N
3)
101
: Invalid
B
110
: Digital input without function
B
111
: Invalid
B
: Invalid
B
Manual, 04/2016, A5E33015755-AC
Bit 0
3)
3)
3)

Hide quick links:

Advertisement

Table of Contents
loading