Table 2-8 Analog Output Configuration Parameters; Figure 2-10 Ao Function Block Example - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.11 AO Function Block,
Configuration Parameters, continued
Properties Group
Block
Order
Address
I/O Module
Channel
Range
Range Hi
Range Low
Output
mA at range
High
mA at Low
range
Example
Figure 2-10 shows a Function Block Diagram configuration using an AO function block to retransmit an
analog input value. In example A, the output is from a SPP block to an external controller via the AO block.
In example B, the mA output is 4 mA for an analog input of 2000.
NOTE: Reverse scaling is required for duplex control outputs.
36
continued

Table 2-8 Analog Output Configuration Parameters

Parameter
Index#
N/A
1
2
3
4

Figure 2-10 AO Function Block Example

Function Block Reference Guide
Parameter Description
Execution Order for Block
Address of selected I/O
module (must match model
selection guide)
Channel on selected I/O
Module
High Range Value
Engineering Unit - value of
input that corresponds to
100% output value
Low Range Value
Engineering Unit - value of
input that corresponds to 0%
output value
Value of mA output that
corresponds to 100% output
signal
(for example: 20mA)
Value of mA output that
corresponds to 0% output
signal
(for example: 4mA)
Value or Selection
Read Only. See "Configure'
Menu, "Execution Order" to
change.
Enter a value:
from 4 to 10
Enter a value:
from 1 to 4
-99999 to 999999
Default = 100
-99999 to 999999
Default = 0.0
0 to 20
Default = 20
0 to 20
Default = 4
3/99