Table 2-57 Tpo Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

2.73 TPO Function Block,
Configuration Parameters, continued
Properties Group
I/O Module
Address
Channel
Range Hi
Range
Range Lo
Cycle Time
Cycle Settings
Min Off Time
Min On Time
Example
Figure 2-77 shows a Function Block Diagram using a TPO function block. Time Proportioning outputs are
commonly used for electrically heated applications where regulating the amount of ON time vs OFF time of
a heater is used to control temperature. In the example the TPO output is used to activate a relay output to
control a heater.
3/99
continued

Table 2-57 TPO Configuration Parameters

Parameter
Index#
0
1
2
3
4
5
Figure 2-77 TPO Function Block Example
Function Block Reference Guide
Parameter Description
Address of selected I/O module
Channel on selected I/O Module
High Range Value
Low Range Value
Output Cycle Time
Minimum OFF time
Minimum ON time
Function Blocks
Value or Selection
Enter a value:
from 1 to 16
Enter a value:
from 1 to 4
-9999 to 9999
Default = 100
-9999 to 9999
Default = 0
1 to 120 seconds
Default = 20
0.0 to 15.0 seconds
Default = 0.0
0.0 to 15.0 seconds
Default = 0.0