7.2. Setting Up the WAGO-I/O-SYSTEM Fieldbus Coupler
Set up the WAGO-I/O-SYSTEM Fieldbus Coupler.
7.2.1.
Hardware Settings
Set the hardware switches on the WAGO-I/O-SYSTEM Fieldbus Coupler.
Precautions for Correct Use
Make sure that the power supply is OFF when you perform the setting up.
Connect the Power supply
1
module, Digital input module,
Digital output module, and End
module to the Fieldbus Coupler
so that the WAGO-I/O-SYSTEM
is created.
In this document, two sets of
2-channel digital output modules
and one 4-channel digital input
module are connected as an I/O
Unit as shown on the right.
* If the power supply is turned
ON, settings may not be
applicable as described in the
following procedures.
Check the position of the
2
hardware switches on the front
panel of the
WAGO-I/O-SYSTEM Fieldbus
Coupler by referring to the right
figure.
Set all the Address Selection
3
Switches to OFF.
* The actual node address is set
by Sysmac Studio.
4
Connect the Ethernet cable to
the Fieldbus connection (X1 IN).
5
Connect the 24 VDC power
supply to the System supply and
to the Field supply.
7.EtherCAT
Power supply module
System supply
Field supply
Fieldbus Coupler
Digital output module
Address Selection
Switch
Fieldbus connection
(X1 IN)
Fieldbus connection
(X1 OUT)
Connection Procedure
Digital input module
End module
Status LEDs
Fieldbus
10