7.5.7

External position sensing system

7.5.7.1
Operating conditions for all device versions
Ambient temperature
● Permissible ambient temperature for operation
Degree of protection
1)
Climate class
● Storage
● Transport
● Operation
) Impact energy max. 1 joule.
1
7.5.7.2
Constructional design for all device versions
How does it work?
● Range of stroke (linear actuator)
● Angle of rotation (part-turn actuator)
Mounting method
● On the linear actuator
● On the part-turn actuator
Material
● Enclosure
Weight, basic device
Torque for plastic cable gland nut
7.5.7.3
Certificates, approvals, explosion protection for all device versions
Electrical data
For connecting to circuits with the
following peak values
Certificates and approvals
CE conformity
SIPART PS2 (6DR5...)
A5E03436655-02, 01/2013
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-40 ... +90 °C (-40 ... +194°F)
IP66 according to EN 60529 / NEMA 4X
According to DIN EN 60721-3-4
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the
positioner axis 16 to 90°)
30 ... 100°
Using the mounting kit 6DR4004-8V and, if required, an
additional lever arm 6DR4004-8L on the actuators as per
IEC 60534-6-1 (NAMUR) with a fin, columns, or a plane
surface.
Using the mounting kit 6DR4004-8D on the actuators with
fastening plane as per VDI/VDE 3845 and IEC 60534-6-2:
The required mount must be provided on the actuator-
side.
Makrolon® glass-fiber reinforced polycarbonate (PC)
Approximately 0.9 kg (1.98 lb)
2.5 Nm
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.