5. WIRING

The following explains the wiring precautions and module connection
example.

5.1 Wiring Precautions

External wiring that is less susceptible to noise is required as a
condition of enabling a highly reliable system and making full use of the
capabilities of Q68RD3-G.
(1) Use separate cables for the AC control circuit and the external
input signals of the Q68RD3-G to avoid the influence of the AC side
surges and inductions.
(2) Always place the RTD at least 100mm away from the main circuit
cables and AC control circuit lines. Fully keep it away from high-
voltage cables and circuits, which include high frequency waves,
such as an inverter's load circuit. Not doing so will cause the
module more susceptible to noises, surges and inductions.
(3) The following wiring is required for the product to comply with the
EMC and Low Voltage Directives.
(a) Use shielded cables for every external wiring and use the
(b) For wiring between A6CON4 and a relay terminal block, use
(c) Before touching the relay terminal block, always touch the
In a control panel
Q68RD3-G
A6CON4
Relay
terminal
block
20(7.87) to 30cm
(11.81 inch)
AD75CK cable clamp to ground to the panel. AD75CK can
ground four cables together when using cables with outer
diameter of about
shielded cables to ground to the panel. In addition, keep the
wiring distance within 3m.
grounded metal to discharge the electricity charged in the
body.
AD75CK
Strip off the
outer sheath
7mm.