Evaporation temperature of medium

Charging control

Increase of the flow
temperature setpoint
Transfer boost
Type of charging

Overtemperature protection

Siemens Schweiz AG
HVAC Products
T
Tkol
TSpSi
TSp
On
Off
TSpSi
Storage tank safety temperature
TSp
Storage tank temperature
TKolUe
Collector temperature for overtemperature protection
TSpmax
Maximum charging temperature
Tkol
Collector temp
On / Off
Collector pump
t
Temperature
t
Time of day
Line no.
Operating line
3860
Evaporation heat carrier
If there is a risk of the heat carrying medium evaporating due to high collector
temperatures, the collector pump will be deactivated to prevent it from exceeding
certain temperature levels. This is a protective pump function.

6.10 DHW storage tank

Line no.
Operating line
5020
Flow setpoint boost
5021
Transfer boost
5022
Type of charging
With B3
With B3/B31
With B3, legio B3/B31
The DHW request to the boiler is made up of the current DHW setpoint plus the
adjustable charging boost.
Heat transfer makes it possible to transport energy from the buffer storage tank to the
DHW storage tank. In that case, the actual buffer storage tank temperature must be
higher than the actual temperature of the DHW storage tank.
The temperature differential can be set here.
The storage tank can be charged using up to 2 sensors.
It is also possible to combine partial charging with 1 sensor and the legionella function
with 2 sensors (setting 3).
Line no.
Operating line
5050
Charging temperature max
Solar energy charges the DHW storage tank up to the adjusted maximum DHW
charging level.
User Manual
The settings in detail
1°C
TSp
TSpMax
TKolUe
1°C
t
CE1U2353en
22. November 2006
69/100