Mounting notes
Mounting method
28/100
Siemens Schweiz AG
HVAC Products
3.7.5
Checking the wireless components
To check whether the connections to the required system components are operational,
consult operating lines 130 through 135 on operating page "Wireless" (operating level
"Commissioning").
3.8 Power supply AVS16.290
The boiler control panel is designed for installation in floor-standing or wall-hung oil or
gas boilers and may only be used for that purpose. For installation, the following points
must be observed:
• Power to the control panel may be supplied only after it is completely fitted in the cut-
out. Extension modules or dummy covers for which cutouts are provided must also
be fitted beforehand
• Dimensions of cutout 92 x 92 mm, sheet metal thickness 0.5 to 3.0 mm
• The boiler control panel must be secured with the 4 clips provided on the panel
• Control panel wiring to the connection terminals does not feature strain relief so that
the cables must be secured inside the boiler
• Local regulations for electrical installation must be complied with
installation