Start function

Collector start function
Min run time collector
pump

Frost protection for the collector

Overtemperature protection for the collector

68/100
Siemens Schweiz AG
HVAC Products
T
TSp
On
OFF
Tkol
Collector temp
On / Off
Collector pump
SdEin
Temperature differential ON
SdAus
Temperature differential OFF
TSp
Storage tank temperature
Line no.
Operating line
3830
Collector start function
3831
Min run time collector pump
If the collector temperature cannot be accurately acquired during the time the pump is
deactivated (especially in the case of vacuum tubes), the pump can be switched on
from time to time.
The function periodically activates the collector pump for at least the selected minimum
running time.
Line no.
Operating line
3840
Collector frost protection
When there is risk of frost at the collector, the collector pump will be activated to
prevent the heat-carrying medium from freezing.
If the collector temperature falls below the frost protection temperature, the
collector pump will be activated: TKol < TKolFrost
When the collector temperature returns to a level of 1 °K above the frost protection
temperature, the collector pump will be deactivated again: TKol > TKolFrost + 1
Line no.
Operating line
3850
Collector overtemp prot
If there is risk of overtemperature at the collector, storage tank charging is continued to
reduce the amount of surplus heat. When the storage tank's safety temperature is
reached, charging will be stopped.