Recooling; Electric Immersion Heater - Siemens Albatros2 RVS46 User Manual

Zone controler
Hide thumbs Also See for Albatros2 RVS46:
Table of Contents

Advertisement

Recooling

Recooling heat gen/HC
Recooling collector

Electric immersion heater

Electric immersion
heater:operating mode
Electric immersion
heater:release
70/100
Siemens Schweiz AG
HVAC Products
The protective collector overtemperature function can reactivate the collector pump
until the maximum storage tank temperature is reached.
Line no.
Operating line
5055
Recooling temperature
5056
Recooling boiler/HC
5057
Recooling collector
Off
Summer
Always
For recooling the DHW storage tank, there are 2 functions available:
• Heating energy can be drawn off either by space heating or the DHW storage tank.
This can be selected separately for each heating circuit (operating page "Heating
circuit 1...")
• If the collector is cold, the energy can be emitted to the environment via the
collector's surfaces
Line no.
Operating line
5060
El imm heater optg mode
Substitute
Summer
Always
5061
El immersion heater release
24h/day
DHW release
Time program 4 / DHW
5062
El immersion heater control
External control thermostat
DHW sensor
Substitute
The electric immersion heater is only used if the boiler delivers a fault status message
or if it has been shut down via boiler lock. This means that in normal situations the
DHW is heated by the boiler.
Summer
The electric immersion heater is used as soon as all connected heating circuits have
switched to summer operation. The DHW is again heated by the boiler as soon as at
least one of the heating circuits has switched back to heating mode. But the electric
immersion heater is also used if the boiler delivers a fault status message or has been
shut down via boiler lock.
Always
DHW is heated with the electric immersion heater throughout the year. This means that
with this application, the boiler is never required for DHW heating.
24h/day
The electric immersion heater is always released, independent of time programs.
Example:
User Manual
The settings in detail
0
6
12
h
18
24
CE1U2353en
22. November 2006

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents