Fisher Rotary Actuators And Sliding-Stem Linear Actuators Over 210 Mm (8.25 Inches) Travel - Fisher FIELDVUE DVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Installation
July 2013
8. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
Note
Ensure that there is clearance between the magnet assembly and the DVC6215 housing slot throughout the full range of travel.
Fisher Rotary Actuators and Sliding‐Stem Linear Actuators over 210 mm (8.25 Inches) Travel
The DVC6215 feedback unit uses a cam (designed for linear response) and roller as the feedback mechanism. See
figures 2‐12 and 2‐13.
Figure 2‐12. Mounting on Rotary Actuators
W9708
Note
All cams supplied with FIELDVUE mounting kits are characterized to provide a linear response.
There are three different mounting adaptions, based on the actuator design (see figure 2‐14).
Fisher Rotary Actuators
Refer to the following guidelines when mounting on rotary actuators.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to
be sure that the above measures stay in effect while working on the equipment.
20
ROTARY MOUNTING
KIT (DVC6215 NOT
SHOWN)
Figure 2‐13. Mounting on Sliding‐Stem (Linear)
Actuators over 210 mm (8.25 Inches) Travel
W9709
Instruction Manual
D103412X012
MOUNTING
ADAPTOR
LONG STROKE
MOUNTING
KIT (DVC6215
NOT SHOWN)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents