Indoor Unit, Outdoor Unit Mismatching Problem; Tank Type Problem - Daikin EBLA04E V Series Service Manual

Table of Contents

Advertisement

3
|
Troubleshooting
3.3.89 UA-00 – Indoor unit, outdoor unit mismatching problem
3.3.90 UA-17 – Tank type problem
Service manual
78
draft – 31/05/2022 15:53
2 For more information about the configuration and further troubleshooting,
see
the
ONECTA
www.onlinecontroller.daikineurope.com/
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Signal transmission
between outdoor and
indoor unit abnormality.
Improper combination of
outdoor and indoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check the wiring between the hydro PCB and the main PCB. See
4
circuit" [
 254].
Possible cause: Faulty wiring between the hydro PCB and main PCB.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
3 Perform a check of the hydro PCB. See
Possible cause: Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
[E-05] is not set as 1, or
[E-07] is not set correctly.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check for improper combination of the indoor unit and the water tank. See
the combination table in the Databook for more information.
app
or
see
Effect
Unit will stop operating.
"4.14 Main
"4.12 Hydro
Effect
Unit will stop operating.
the
website:
http://
Reset
Power reset via outdoor
unit.
"5.1 Electrical
4
PCB" [
 184].
4
PCB" [
 175].
Reset
Power reset via outdoor
unit.
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05