16 Point Analog Output
Step
4
Connect field wiring.
RTP A for
Outputs 1 to 8, 9+ and 10+
RTP B for
Outputs 11 to 16, 9- and 10-)
16 Point Analog Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP labeled "DI, DO, AO RTP ASSY" with jumpers J2-J9 is the correct one for 16
point AI.
Mount RTP cable assembly to HC900 Controller (Figure 96).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 85.
Connect terminal block end of desired cable assembly to 16 point Analog Input module at controller.
Choose from:
900RTC-3210
900RTC-3225
Install 16 point Analog Input label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 81).
Revision 6
21 April 2017
ETC.
1
2
3
4
5
6
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
1
2
3
4
5
6
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
External 24VDC supply
Remote Terminal Cable assembly, 1.0 meters long
Remote Terminal Cable assembly, 2.5 meters long
HC900 Process & Safety Controller User and Installation Manual
Action
LOADS ARE 0 to 750 ohm
9 10 11 12 13 14 15 16 17 18 19 20
7
8
9 10 11 12 13 14 15 16 17 18 19 20
7
8
EXT +24V Install 24V wires as shown:
EXT 24V RTN
Action
22 to 10
22 to 12
24VRTN to 9
24VRTN to 11
245