16 Point Contact Digital Input
Step
4
Connect field wiring.
16 Point DC Digital Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP combines the two groups of 8 inputs into one group of 16.
Mount RTP cable assembly to HC900 Controller (Figure 96).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 85.
Connect desired cable to 16 point DC DI module at controller. Choose from:
900RTC-L010
900RTC-L025
900RTC-L050
Install 16 point DC DI module label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 81).
2
Mount RTP to DIN rail.
Latch to rail. See page 253.
Connect cable to RTP.
232
1
2
3
4
5
6
7
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
HC900 Process & Safety Controller User and Installation Manual
Action
8
9 10 11 12 13 14 15 16 17 18 19 20
Install jumper wires
Action
Revision 6
21 April 2017