Honeywell HC900 User And Installation Manual page 126

Process and safety controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Reverse-Polarity Protection
A potential of  34 Volts will cause no damage to the module; a reverse polarity power supply connection
allows continuous current flow to the loads that are not controlled by the On/Off state of the output circuits.
Jumper Comb
Two-position jumper combs are available (as an option for barrier style terminal blocks only) for
connecting digital common wiring between terminals 10 and 12, and for connecting +24Vdc between
terminals 9 and 11. See Figure 61.
+V Terminals
The +V1 (terminal 9) and +V2 (terminal 11) are the positive power supply input to power the output
circuits for the two groups of eight inputs per group. The +V supply must provide minimum 24 Vdc at 65
mA (min) per group.
Hazardous voltages exist at terminal blocks.
Using switches at field devices disconnect the field wiring from power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.
112
HC900 Process & Safety Controller User and Installation Manual
Revision 6
21 April 2017

Advertisement

Table of Contents
loading

Table of Contents