Status
Ready (H200) DC link (H201)
Green/orange
–
or
Red/orange
Hazardous DC link voltages may be present at any time regardless of the status of the "DC
link" LED.
The warning information on the components must be carefully observed!
3.1.6
5 kW and 10 kW Smart Line Modules
Table 3-8
5 kW and 10 kW Smart Line Modules – description of the LEDs
LED
Color
READY
–
off
Green
Continuous
Yellow
Continuous
Red
Continuous
DC LINK
–
off
Yellow
Continuous
Red
Continuous
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when
component recognition is activated via p0124 = 1.
DANGER
Status
Electronics power supply is missing or outside
permissible tolerance range.
Component is ready to operate.
Pre-charging not yet complete.
bypass relay dropped out
EP terminals not supplied with 24 V DC.
Overtemperature
Overcurrent switch-off
Electronics power supply is missing or outside
permissible tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
Line supply fault.
Description, cause
Description, cause
Diagnosis
3.1 Diagnostics via LEDs
Remedy
–
Remedy
–
–
–
Diagnose fault (via output
terminals) and
acknowledge it (via input
terminal)
–
–
Check the supply voltage.
117