Active Line Module - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
Orange
OUT>5 V
-
Orange
MOD
-
3.1.4

Active Line Module

Table 3-6
Active Line Module - description of the LEDs
Status
Ready (H200) DC link (H201)
off
off
Green
off
Orange
Red
Orange
Orange
Red
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Status
Flashing
Firmware CRC error.
2 Hz
off
Electronics power supply is missing or outside
permissible tolerance range.
Power supply v5 V
Continuous
Electronics power supply for measuring system
available.
Power supply >5 V.
Important:
Make sure that the connected encoder can be
operated with a 24 V power supply. If an encoder
that is designed for a 5 V supply is operated with a
24 V supply, this can destroy the encoder
electronics.
off
Reserved
Description, cause
Electronics power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Description, cause
Diagnosis
3.1 Diagnostics via LEDs
Remedy
Make sure that the
CompactFlash card
has been inserted
properly.
Replace the
CompactFlash Card.
Replace Control Unit.
Carry-out a POWER
ON.
-
-
-
Remedy
Check line voltage
Remedy and acknowledge
fault
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents