Four Way Valve Abnormality - Daikin FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU Service Manual

Inverter pair ceiling mounted cassette type ffq-q series
Table of Contents

Advertisement

Troubleshooting

4.19 Four Way Valve Abnormality

EA
Error Code
Method of Error
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Detection
Error Decision
The following condition continues over 10 minutes after operating for 5 minutes.
Conditions
Supposed
Causes
85
Cooling/Dry
A – B < –5°C (A – B < –9°F)
Heating
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
SiUS091628EA
Service Diagnosis