Discharge Pipe Temperature Control - Daikin FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU Service Manual

Inverter pair ceiling mounted cassette type ffq-q series
Table of Contents

Advertisement

Control Specification
2.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
35
B
C
D
Discharge pipe
temperature
09/12 class
(°C)
(°F)
A
110
230.0
B
103
217.4
C
98
208.4
D
93
199.4
E
88
190.4
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
15/18 class
(°C)
(°F)
110
230.0
103
217.4
101.5
214.7
100
212.0
95
203.0
Control
SiUS091628EA
Stop zone
A
Dropping zone
Keep zone
Up zone
E
Reset zone
(R23013)
Functions and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents