Service Diagnosis
3.2
Wireless Remote Controller Kit (BRC082A41W,
BRC082A42W(S))
Relations
The following modes can be selected by using INSPECTION/TEST OPERATION button on the
remote controller.
Between Modes
Indoor unit settings can be made.
Filter cleaning sign time
Others
Press INSPECTION/TEST
OPERATION button once.
Following codes can be checked.
Error codes
Indoor model code
Service
To find the error code, proceed as follows:
Diagnosis
59
Field
setting
mode
Press INSPECTION/TEST
OPERATION button for more
than 4 seconds.
Press INSPECTION/TEST
OPERATION button once.
Inspection
mode
Step
Action
1
Press INSPECTION/TEST OPERATION button to enter the inspection mode. Then the
figure 0 blinks on the UNIT No. display.
Press INSPECTION/TEST
OPERATION button for
Service
more than 4 seconds.
mode
Press INSPECTION/TEST
OPERATION button once.
Normal
mode
After 10 seconds without starting test operation
or press INSPECTION/TEST OPERATION button once
or 30 min. after the test operation start
After 60
seconds
Test
operation
Press INSPECTION/
mode
TEST OPERATION
button once.
INSPECTION/TEST
OPERATION button
SiUS091628EA
Service data can be obtained.
Error code history
Temperature data of various sections
Service settings can be made.
Forced fan ON
Airflow rate setting
Press ON/OFF button within 10 seconds
to start test operation.
Thermostat is forcibly turned on.
Test operation will stop automatically
after 15~30 minutes.
(R24049)
(R24050)
Service Diagnosis