4�3 Configuring the XNX Universal Transmitter
The XNX Universal Transmitter can be configured via the front panel by using the
menus available in the Configure Menu. For information on accessing and navigating
the menus, see Section 5.1 - Controls and Navigation.
The XNX is shipped with the following settings:
Display Language
Date Format
Time Format
mA Sensor Type (w/IR Personality)
mV Sensor Type (w/mV personality) MPD-IC1 (%Vol)
Alarm Levels
Latching/Non-Latching Alarms
Display Units
4-20 mA Levels
Calibration Interval
Unit ID
Relay Settings
Fieldbus Settings
Level 1 Password Access
Level 2 Password Access
Easy Reset Enabled
38
HART
®
Modbus
®
(if installed)
English
mm/dd/yy
HH:MM
Searchpoint Optima Plus
Sensor Cartridge Dependent
Alarm: Latching
Fault: Non-Latching
PPM, %VOL or %LEL
(dependent on personality and sensor choice)
Inhibit: 2.0 mA
Warning: 3.0 mA
Overrange: 21.0 mA
180 Days (HA recommends 30 day interval)
XNX #nnnnnnnn
Alarm Normally De-Energized
Address: 0
Mode: Point-To-Point
Address: 5
Baud Rate: 19200
0000
0000
Yes
XNX Universal Transmitter Quick Start Guide