11 Informational Messages

Information
Number
I001
Unused
I002
Force Relay Mode Started
I003
Force Relay Mode Ended.
I004
Force mA Mode Started
I005
Force mA Mode Ended
I006
Short-Term Inhibit Started
I007
Short-Term Inhibit Ended
I008
Long-Term Inhibit Started
I009
Long-Term Inhibit Ended
I010
mA Output Recalibrated
I011
Bump Test Started
I012
Bump Test Timed Out
I013
Bump Test Completed Concentration < Al1
I014
Bump Test Completed
Al1 < Concentration < Al2
I015
Bump Test Completed. Al2 < Concentration
I016
Zero Calibration Successful
I017
Zero Calibration Failed
I018
Calibrate Span Successful 1 of 2
I019
Calibrate Span Successful 2 of 2
I020
Calibrate Span Failed
I021
Calibrate Span Timeout
I022
Password Changed
I023
Performing Soft Reset
I024
Alarms Configured Latching
I025
Alarms Configured Non-Latching
I026
Alarm Relays Configured Normally Energized
I027
Alarm Relays Configured Normally De-
Energized.
I028
Fieldbus Address Changed
I029
Fieldbus Speed Changed
I030
Sensor Type Changed
I031
Gas Selection Changed
I032
Time For Beam Block Fault Changed
I033
Time For Fault Detection Changed
I034
Level For Low Signal Fault Changed
I035
Invalid Path Length Written
I036
Path Length Changed
XNX Universal Transmitter Quick Start Guide
Description
Contents of Data Field
Bitpattern for relays. (E.G. 7.0 ==All)
N/A
Force current. (E.G. 20.0)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Peak concentration observed
Peak concentration observed
Peak concentration observed
N/A
Error code
Percent change in span factor from previous
Absolute span factor
Error code
N/A
1,2 or 3 (access level)
N/A
N/A
N/A
N/A
N/A
New address (e.g. 15)
New speed (e.g. 19200)
iCurrentCalGlobalID
iCurrentCalGlobalID
iBlockFltTime
iOtherFltTime
fLowSignalLevel
fPathLen
fPathLen