2�6 Ec Personality Wiring - Honeywell XNX Quick Start Manual

Universal
Hide thumbs Also See for XNX:
Table of Contents

Advertisement

2�6 EC Personality Wiring
WARNING
When the XNX is equipped with the optional Remote Mount Kit, the remote sensor
MUST be securely mounted to a fixed position. The Remote Sensor Kit is not
intended to be used as a hand-held detector.
J1
LOCAL
HART
20 mA
Operation
S1
S2
Source
Sink
S1
S2
Isolated
+V 1-1
1-2
-V 1-3
1-4
+mA 1-5
-mA 1-6
EC
TB-1
EC Barrier
J2
Figure 10. XNX EC Personality Board Terminal Blocks and Jumper Switches and
cAutIoN
Be certain to dress the wires properly to ensure cabling does not contact switches
1-2 on the back of the POD.
Do not force the POD into the enclosure as it may indicate an interference condition
resulting in damage to the wiring, POD or switch settings.
XNX Universal Transmitter Quick Start Guide
J1 - Local HART Connector
S1 and S2 - Signal Output
Source
Sink
Isolated
J2 - EC Barrier Connector
XNX EC TB-1
Terminal Block Assignments
Jumper Switch
S1
S2
Position
EC
TB1
1
+24
2
3
0v
4
17