Omron NB3Q-TW00B Startup Manual Manual page 94

Nb-series programmable terminals
Hide thumbs Also See for NB3Q-TW00B:
Table of Contents

Advertisement

6 Maintenance and Troubleshooting
For example, the addresses for changing the password online are provided below:
LW10022~10023 Password for safety level 0, Retentive 2 words
LW10024~10025 Passowrd for safety level 1, Retentive 2 words
LW10026~10027 Password for safety level 2, Retentive 2 words
LW10118~10143 Password for safety level 3~15, Retentive 2 words * 13.
If the level 2 password needs to be changed, set in the software as follows: First, place a Number Input
component on window, check [System Memory], then select LW10026, as shown below
Select [Password] for the Data Type in the attributes page of [Numeric Data], as follows:
The process is the same for changing other system parameters online. But note that after changing the
following system parameters, the PT needs to be rebooted to validate the changes.
System Parameter Setting: the following addresses will take effect after reboot.
Addresses
10010
10011
10013
10014
10015
10016
10017
10018
6-6
Descriptions
Initial Screen number
Screen saver (backlight saver)
Common Sheet/Pop-up Screen
Common Sheet/attribute
Storage event number
RTC source
Default language
System reserve
comments
0~65535
0 (OFF, Constant, Screen saver inactivated)
1~600 minutes (activated)
0: Normal
1: Higher than other screens
0: Lower than the Base screen
1: Higher than the Base screen
0~65535
0: PLC(Local Word)
1: Internal RTC
0~3
HMI internal use
NB-series Programmable Terminals Startup Guide Manual(V109)