Table 5-16 Quick Commissioning - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Performing Quick Commissioning via OP
For applications using V/f (P1300 = 0 [default]) or Flux Current Control (FCC) (P1300 = 1 or
6), quick commissioning can be accomplished by setting the following parameters:
Enter the line frequency
Enter the rating label data P0304,
Command and setpoint sources
Minimum and maximum frequency
Ramp-up and ramp-down times
Closed-loop control mode
Motor data identification
For applications using Vector Control (P1300 = 20 ... 23), the parameters in the following
flow chart should be set and used:
Parameters designated with an "*" offer more settings than are actually shown here. Refer to
the Parameter list for additional settings.
Table 5-16
Quick commissioning
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
P0003 = 3
User access level*
1: Standard: Allows access into most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0004 = 0
Parameter filter*
0: All parameters
2: Inverter
3: Motor
4: Speed sensor
P0010 = 1
Commissioning parameter filter*
0: Ready
1: Quick commissioning
30: Factory setting
Note: P0010 should be set to 1 in order to parameterize the data of the motor rating plate.
P0100 = 0
Europe/North America (enter the motor frequency)
0: Europe [kW], frequency default, 50 Hz
1: North America [hp]. frequency default, 60 Hz
2: North America [kW], frequency default, 60 Hz
P0205 = 0
Inverter application (enter the required overlaod)
0: High overload (for compressors, processing machines, etc.)
1: Light overload (for pumps and fans, etc.)
Note: This parameter is only effective for Inverters ≥ 5.5 kW/400 V.
P0230 = 0
Output filter (Shows the selected output filter)
0: no filter
1: output choke
3 internal LC filter
4: external output LC filter
P0233 = ?
Filter inductance
inductance of the used output filter (phase value)
can only be set, if an external output filter is selected (P230 = 4)
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
Commissioning (software)
5.7 Commissioning modes
P0100
P0304, P0305, P0307, P0310 and P0311
P0700, P1000
P1080, P1082
P1120, P1121
P1300
P1900 = 3
Setting
5-21