Setting the PROFIBUS DP address via DIP switches
The PROFIBUS DP address can be set via DIP switch, as shown in the table below.
Table 4-1
DIP switch
Add to address
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
4.3.2
Connecting the PROFIBUS DP
Connecting the Inverter to the PROFIBUS DP network
The inverter is to be connected to the PROFIBUS DP network via a sub-D socket on the
CU240S DP or CU240S DP-F. The pins of the socket are short-circuit-proof and isolated.
Table 4-2
External 24 V supply
If the PROFIBUS DP interface is required to communicate with the Control Unit when the
Power Module mains power is not present, a 24 V supply must be connected to the Control
Unit terminals 31 (+ 24 V I
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
4.3 Connecting a CU240S DP or CU240S DP-F via PROFIBUS DP
Example address for the PROFIBUS DP interface
PIN assignment of the 9-pin sub-D socket
Pin
Designation
1
Shield
2
U0V
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP
7
U24V
8
RxD/TxD-N
9
-
Case
Cable shield
) and 32 (0 V I
n
1
2
1
2
Meaning
Ground connection
Isolated and user supply reference
Receive/send data P (B/B')
Control Signal
PROFIBUS data reference potential (C/C')
Supply voltage positive
Isolated user supply +24 V @ 100 mA
Receive/send data N (A/A')
Not assigned
Cable shield
).
n
Installing/Mounting
3
4
5
6
4
8
16
32
Range
RS485
TTL
5 V ± 10 %
RS485
7
64