Commissioning (software)
5.7 Commissioning modes
5.7.4.4
Series commissioning with MMC
Upload and download a parameter set with an MMC
A parameter set can be uploaded from an inverter and then downloaded into another
inverter. The following important restrictions must be considered when using the copying
procedure:
● An inverter with an apropriate parameter set is available (upload inverter)
● The upload inverter can be accessed via OP, STARTER or PROFIBUS
● An MMC Type 6SL3254-0AM00-0AA0 is available.
5-52
Note
During a parameter download from a MMC to the EEPROM of the Control Unit (e.g.
during serial commissioning) normally the LEDs are flashing.
If the Control Unit is in a faulty state, the fault will be displayed by the LEDs (SF on, RDY
off), although the download is performed.
If the parameter download has been performed successfully F0395 appears.
Operating Instructions, 11/2006, A5E00766042B AA
Control Units CU240S