Table 3-4 Settings Of The General I/O Dip Switches - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Figure 3-6
General I/O DIP switches (CU240S, CU240S DP and CU240S DP-F)
There are seven general I/O DIP switches that allow the settings described below.
In the factory setting the I/O DIP switches are in the OFF position.
Figure 3-7
Table 3-4
Settings of the General I/O DIP switches
DIP switch
1
Meaning
AI0
ON
0 mA ...
20 mA
OFF
-10 V ...
+10 V
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
CU240S DP-F Control Terminals
2
3
4
5
6
General I/O DIP switches
2
3
AI1
24 V Encoder
supply
0 mA ...
24 V
20 mA
0 V ... 10 V
0 V
3.5 Interfaces of the CU240S variants
7
4
5
5 V Encoder
Encoder A
supply
termination
5 V
Encoder A
ON
0 V
Encoder A
OFF
Description
6
7
Encoder B
Encoder Z
termination
termination
Encoder B
Encoder Z
ON
ON
Encoder B
Encoder Z
OFF
OFF