5.5

Parameterization with MMC

Overview
A G120 inverter can be parameterized by downloading a parameter set from the MMC to the
inverter.
The download can be performed as
● manual download
● automatic download
● start-up download
A detailed download description can be found in the operation section.
Note
The file format for the MMC is FAT. Any other format, such as FAT32 or NTFS are not
compatible with uploading and downloading parameter sets from the inverter.
Formatting can be accomplished using the DOS command line as follows:
C:\>format volume /FS:FAT - where volume has to be replaced by the name of the MMC
drive, for example A
Please keep in mind that formatting will delete all the contents of the MMC.
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
Commissioning (software)
5.5 Parameterization with MMC
5-15