9-3-4. Wiring Connection
1. Remove the electric parts cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) with water
coming in the outdoor unit. Process them so that
they do not touch any electrical or metal parts.
Stripping length of connecting cable
Terminal block
40
Connecting
Power
cable
cord
Fig. 9-3-9
Model
RAS-10JKVP-E
Power source
Maximum running current
Installation fuse rating
Power cord
Connection cable
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local requlations/codes
when running the wire from outdoor unit to
indoor unit. (Size of wire and wiring method etc.)
• Every wire must be connected firmly.
• This installation fuse (25A D type
be used for the power supply line of this air
conditioner.
• If incorrect or incomplate wiring is carried out, it
will cause an ignition or smoke.
• Prepare the power supply for exclusive use with
the air conditioner.
• This product can be connected to the main
breaker.
Connection to fixed wiring : A switch which
disconnects all poles and has a contact separa-
tion of at least 3 mm must be incorporated in the
fixed wiring when connecting to a main breaker
circuit.
NOTE : Connecting cable
• Wire type : More than H07RN-F or 245IEC66
(1.0mm² or more)
10
1 2 3
10
L N
10
10
30
30
Earth line
Power
Connecting cable
cord
RAS-13JKVP-E
220 – 240 V~, 50 Hz
220 V~, 60 Hz
10A
11A
25A (D type
)
H07RN-F or 245IEC66
(1.5 mm² or more)
Wire type: More than
H07RN-F or 245IEC66
(1.0 mm² or more)
) must
9-3-5. Gas Leak Test
Prüfpunkte für
das
Innenraumgerät
Abdeckung der
elektrischen Anschlüsse
40
• Check the flare nut connections for the gas leak with
a gas leak detector or soap water.
9-3-6. Test Operation
To test the system, push and hold RESET button for
10 sec. (There will be one short beep.)
9-3-7. Auto Restart Setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating
mode as before the power failure.
Information
The product was shipped with Auto Restart
function in the off position.
Turn it on as required.
How to Set the Auto Restart
• Push and hold the RESET button for about 3 sec-
onds. After 3 seconds, three short electronic beeps
wll be heard to inform you that the Auto Restart has
been selected.
• To cancel the Auto Restart, follow the steps de-
scribed in the section Auto Restart Function of the
Owner's Manual.
– 51 –
Ventilabdeckung
Prüfpunkte für das Außengerät
Fig. 9-3-10
Fig. 9-3-11