Intelligent Function Module Interrupt Point Settings - Mitsubishi QD51-R24 User Manual

Melesec q series
Hide thumbs Also See for QD51-R24:
Table of Contents

Advertisement

5 SETTINGS AND PROCEDURES UP UNTIL OPERATION

5.6.3 Intelligent function module interrupt point settings

5 - 16
Here, the interrupt pointer settings in GX Developer for sending and receiving data with
a BASIC program by an interrupt program are explained.
[Purpose of settings]
Intelligent function module interrupt pointer settings set information for starting a
programmable controller CPU interrupt program from a BASIC program.
By carrying out these settings, it becomes possible to start an interrupt program
from a BASIC program and transfer data to the programmable controller CPU.
[Start procedure]
[PC Parameter]
For the screen display method, refer to the GX Developer Operating Manual.
[Setting screen]
[Display contents]
(1)
CPU Side Interrupt Pointer Header No.
This sets the header No. (50 to 255) of the interrupt pointer (I
sequence program.
(2)
CPU Side Interrupt Pointer Count
This sets the number (1) of interrupt pointers (I) used in the sequence program.
(3)
Intelligent Function Module Side Header I/O No.
Sets the QD51 (-R24)'s header I/O No..
(4)
Intelligent Function Module Side Header SI No.
1)
Creates a correspondence between the QD51 (-R24)'s control No. (SI)
and the interrupt pointer (I
2)
Sets the header SI No. (0) of the interrupt control No..
[PC System Settings]
) used in the sequence program.
xx
MELSEC-Q
Interrupt Pointer Settings
xx
) used by the
5 - 16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd51

Table of Contents