Installation

A simplified installation is shown below. This installation is not EMC compliant. For European
installations and countries with EMC legislation refer to the 890 Engineering Reference Manual,
Appendix C.
C
D
P
L1
L
L2
L3
P
G
KEY
B
Back-plate
C
Cubicle
Control Wiring
D
terminals
Supply
G
Protective
Earth/Ground
Motor
K
(M1, M2, M3)
3 Power
L
Supply Cable
(L1, L2, L3)
Fuse or circuit
P
breaker
G
24V
* Permanent Earthing
The unit must be permanently earthed according to EN 50178: For
permanent earthing, one conductor, PE1, of >10mm² cross-section is
required; or two individual incoming protective earth conductors, PE1 &
PE2, of <10mm² cross-section. Each earth conductor must be suitable for
the fault current according to EN 60204.
PE2
890SD
X12/01
X14/04
0V
*
PE1
M1
M2
M3
K
PE2
890SD
X12/01
X14/04
0V
B
*
PE1
M1
M2
M3
K
Page 9