Man Output Setting (Buffer Memory Address: 33 H , 53 H , 73 H , 93 H ); Setting Change Rate Limiter Setting (Buffer Memory Address: 34 H , 54 H , 74 H , 94 H ); At Bias Setting (Buffer Memory Address: 35 H , 55 H , 75 H , 95 H ) - Mitsubishi Electric MELSECSystem Q User Manual

Q64tctt;q64tcttbw; q64tcrt;q64tcrtbw
Table of Contents

Advertisement

3 SPECIFICATIONS
3.5.25 MAN output setting (buffer memory address: 33
3.5.26 Setting change rate limiter setting (buffer memory address: 34
3.5.27 AT bias setting (buffer memory address: 35
3 - 41
(1) This area is used to set the manipulated value in the "MAN" mode.
(2) Write a value to the MAN output setting buffer memory after confirming that the
corresponding bit of the manual mode shift completion flag (buffer memory
address: 1E
) has turned to 1 (ON).
H
If this setting is made when the manual mode shift completion flag is off, the
system will rewrite it to the manipulated value calculated by PID operation.
(1) This setting is made to set the variation of the set value per minute to a set value
(SV) change. This will suppress a derivative kick (sudden change in the
manipulated value).
Process value (PV)
Set value (SV) 2
Set value (SV) 1
(2) Make this setting as a percentage of the input range setting (buffer memory
address: 20
, 40
H
The setting range is 0 to 1000 (0 to 100.0%/min).
(1) This setting is made to perform auto tuning centering on a shifted point (AT point).
Make this setting when shifting the point of the set value (SV) for auto tuning.
Make this setting if an excess of the process value over the set value (SV) will be
inconvenient for auto tuning.
(2) Set the range which has minimal PID operation fluctuations and will not affect the
control results.
Otherwise, exact PID constants may not be provided depending on the object to
be controlled.
[Setting of AT bias on negative side (for reverse action)]
Process value (PV)
Set value (SV)
AT point
(3) The setting range is ±input range.
, 53
H
Setting change rate limiter setting
1 minute
, 60
, 80
) to the full scale.
H
H
H
, 55
H
H
, 73
, 93
)
H
H
H
, 54
, 74
H
H
, 75
, 95
)
H
H
AT bias setting
t
MELSEC-Q
, 94
)
H
H
t
3 - 41

Advertisement

Table of Contents
loading

Table of Contents