Event Log Connections; Installing The 4286 Vip Module; Figure 3-26: Wiring The Vistakey - Honeywell VISTA-32FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.

Event Log Connections

This system has the ability to record up to 512 events of various categories in the Event Log (history log) of various
categories in the Event Log (history log). Each event is recorded with the time and date of its occurrence (if real-time
clock is set).
The categories are Alarm, Supervisory/Check, Bypass, Open/Close, System and Test conditions. The log may be viewed
on an alpha keypad, the GUI or printed on a serial printer.
NOTE: If you are using a serial printer, it must configured with 7 data bits, even parity, 1 stop bit, 9600 baud

Installing the 4286 VIP Module

The 4286 VIP Module is an add-on accessory that permits the user to access the security system (and relays) via a
TouchTone telephone. This may be done either from the premises or by calling the premises from a remote location.
Only one VIP Module can be used in a security system. This module must be enabled as Device Address 4 in the Device
Programming in #93 Menu Mode, and must be assigned to a partition.
U L
The 4286 VIP Module is not permitted in UL installations.
Detailed operating instructions for phone access to the security system are provided with the VIP Module.
1
2 3 4 5 6 7 8 9 10
11 12
TB 1
K1
DOOR
CONTROL
RELAY
1
2
3
4
TB 3
5
6
7
8
VISTAKEY

Figure 3-26: Wiring the VistaKey

49
14V MAX (12V @ 85-160mA Nominal)
GND
POLLING LOOP +
POLLING LOOP -
GND
ZONE A (DSM)
ZONE B (RTE)
ZONE C (General)
GND
POLE Door Strike/Mag Coil
N/C MAG COIL POWER
N/O DOOR STRIKE POWER
RELAY CONTACT RATINGS:
3A @ 28VDC MAX. (RESISTIVE LOAD)
READER INTERFACE CABLE
RDR LED
(ORANGE)
GND
(BLACK)
DATA 1
(WHITE)
DATA 0
(GREEN)
GND
+5V
+12V
(RED)
TRIGGER (SEE NOTE 3)
+
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
NO
CONNECTION