Issue 10/03
In order to ensure a straightforward, successful commissioning, it is important that
the circuit connection in the motor terminal box (refer to Fig. 3-22) matches the
rated motor voltage entered in P0304.
Three-phase motor connection
W2
U1
230 V
U1
V1
W1
Delta connection
Fig. 3-22
Contrary to the BOP, AOP operator panels or the commissioning program
DriveMonitor, the STARTER commissioning (start-up) program offers a mask-
orientated quick commissioning, which is especially advantageous for users who
are using MICROMASTER for the first time. On the other hand, BOP, AOP and
DriveMonitor offer, in conjunction with the drive inverter, parameter-orientated
quick commissioning where the user is navigated through the menu tree mentioned
above.
NOTE
The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
3AC 230/400 V
W2
U2
U2
V2
U1
V1
V1
W1
400 V
Line
U1
V1
W1
Star connection
Motor terminal box
3AC 400/690 V
V2
W2
U2
W1
U1
V1
400 V
U1
V1
W1
Delta connection
3 Functions
W2
U2
V2
V2
U1
V1
W1
W1
Line
690 V
U1
V1
W1
Star connection