Issue 10/03
P0010 = 1
P0100 = 0
P0100 = 1, 2
P0100 = 0
P0205 = 0 P0205 = 0
P0300 = 1 P0300 = 1
P0304 = ? P0304 = ?
P0305 = ? P0305 = ?
P0307 = ? P0307 = ?
P0308 = ?
P0309 = ?
P0310 = ?
P0311 = ?
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Commissioning parameter filter *
0
Ready
1
Quick commissioning
30
Factory setting (refer to Section 3.5.7)
NOTE:
P0010 should be set to 1 in order to parameterize the data of the motor
rating plate.
Europe/ North America (enters the line supply frequency)
0
Europe [kW], frequency default, 50 Hz
1
North America [hp], frequency default, 60 Hz
2
North America [kW], frequency default, 60 Hz
NOTE:
For P0100 = 0 or 1, the setting of switch DIP2(2) determines the value
of P0100 (refer to the parameter list):
OFF = kW, 50 Hz
ON = hp, 60 Hz
Inverter application (enters the required torque)
0
Constant torque
(e.g. compressors, processing machines)
1
Variable torque
(e.g. pumps, fans)
NOTE:
This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V.
Select motor type
1
Asynchronous motor (induction motor)
2
Synchronous motor
NOTE:
For P0300 = 2 (synchronous motor), only the V/f control types (P1300
< 20) are permitted.
Rated motor voltage
(entry according to the rating plate (Fig. 3-21) in V)
The rated motor voltage on the rating plate must be checked, regarding
the star/delta circuit configuration to ensure that it matches with the
circuit connection configured at the motor terminal board.
Rated motor current
(entry according to the rating plate (Fig. 3-21) in A)
Rated motor power
(entry according to the rating plate (Fig. 3-21) in kW / hp).
If P0100 = 0 or 2, the entry is in kW and for P0100 = 1, in hp.
Rated motor cosPhi
(entry according to the rating plate (Fig. 3-21) cos ϕ).
If the setting is 0, the value is automatically calculated.
Rated motor efficiency
(entry according to the rating plate (Fig. 3-21) in %).
If the setting is 0, the value is automatically calculated.
Rated motor frequency
(entry according to the rating plate (Fig. 3-21) in Hz).
The number of pole pairs is automatically calculated.
Rated motor speed
(entry according to the rating plate (Fig. 3-21) in RPM)
If the setting is 0, the value is internally calculated.
NOTE:
An entry must be made for closed-loop Vector control, V/f control with
FCC and for slip compensation.
3 Functions
75