Load Torque Monitoring - Siemens MICROMASTER 440 Operating Instructions Manual

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

3 Functions
3.19.2

Load torque monitoring

Parameter range:
Warnings
Faults
Function chart number:
This function allows the mechanical
force transmission between the motor
and driven load to be monitored.
Typical applications include, for
example, pulley belts, flat belts or
chains, or pulleys for toothed wheels
of drive-in and drive-out shafts which
then transmit circumferential velocities
and circumferential forces (refer to
Fig. 3-66). The load torque monitoring
function can then detect whether the
driven load is locked or the force transmission has been interrupted.
For the load torque monitoring function, the actual frequency/torque characteristic
is compared with the programmed frequency/torque characteristic (refer to P2182 –
P2190). If the actual value lies outside the programmed tolerance bandwidth, then,
depending on parameter P2181, either warning A0952 or fault F0452 is generated.
Parameter P2192 can be used to delay the output of the warning or fault message.
This avoids erroneous alarms which could be caused by brief transient states (refer
to Fig. 3-67).
Torque [Nm]
P2189
P2190
P2187
P2188
P2185
P2186
1
r2198
Bit 11
0
Fig. 3-67
156
P2181
P2182 – P2192
r2198
A0952
F0452
-
P2182
P2183
P2192
Load torque monitoring (P2181 = 1)
Fig. 3-66
Shaft drive with flat belts
P1082
Actual
torque
Frequency
[Hz]
P2184
A0952
P2192
MICROMASTER 440
Issue 10/03
Drive
shaft
Deflection
roll
t
Operating Instructions
6SE6400-5AW00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents