Issue 10/03
Determine the
motor parameter
outside the quick
commissioning ?
no
yes
With pulse encoder ?
no
yes
Select encoder type
P0400 = 0 P0400 = 1
Number of encoder pulses
P0408 = ?
Enters the number of encoder pulses per revolution. The number of
encoder pulses per revolution P0408 is limited by the max. pulse
frequency of the pulse encoder module (f
Technical application
P0500 = 0
Defines the technical application and the control mode (P1300).
With temperature
sensor ?
no
yes
Motor temperature sensor
P0601 = 0 P0601 = 2
Threshold motor temperature
P0604 = ?
Enters the warning threshold for motor overtemperature protection. The
trip temperature (threshold) where either the drive inverter is tripped or
Imax is reduced (P0610) always lies 10 % above the warning threshold.
Motor I
P0610 = 2
Defines the reaction when the motor temperature reaches the warning
threshold
Selection of command source
P0700 = ?
This selects the digital command source.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Refer to Section 3.5.3 "Calculating the motor / control data"
From "Calculating the motor / control parameter"
0
Disabled
1
Single-channel encoder
2
Two quadrature encoder (two channels)
0
Constant torque
1
Pumps and fans
3
Simple positioning
0
No sensor
1
PTC thermistor
2
KTY84
2
t temperature reaction
0
No reaction, only a warning
1
Warning and I
reduced
max
(this results in a reduced output frequency)
2
Warning and trip (F0011)
0
Factory default setting
1
BOP (keypad)
2
Terminal
4
USS on BOP link
5
USS on COM link
6
CB on COM link
= 300 kHz).
max
3 Functions
87