Selection of frequency setpoint
P1000 = ?
Example
P1000=1
P1000=3
P1000=2
Type of ADC
P0756 = 0
Defines the type of the analog input and also enables analog input
monitoring.
NOTE
The following applies for P0756 to P0760:
Index 0 : Analog input 1 (ADC1), terminals 3, 4
Index 1 : Analog input 2 (ADC2), terminals 10, 11
Value x1 of ADC scaling
P0757 = 0
[V/mA]
Value y1 of ADC scaling
P0758 = 0.0
This parameter represents
the value of x1 as a % of
P2000 (reference frequency).
Value x2 of ADC scaling
P0759 = 10
[V/mA]
Value y2 of ADC scaling
P0760 = 100
This parameter represents
the value of x2 as a % of
P2000 (reference frequency).
Setpoint memory of the MOP
P1031 = 0
The last motorized potentiometer setpoint, which was active before the
OFF command or switching-off, can be saved.
Inhibit reverse direction of MOP
P1032 = 1
Setpoint of the MOP
P1040 = 5
Defines the setpoint for the motorized potentiometer (MOP).
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
0
No main setpoint
1
MOP setpoint
2
Analog setpoint
3
Fixed frequency
4
USS on BOP link
5
USS on COM link
6
CB on COM link
7
Analog setpoint 2
0
Unipolar voltage input (0 to +10 V)
1
Unipolar voltage input with monitoring (0 to 10 V)
2
Unipolar current input (0 to 20 mA)
3
Unipolar current input with monitoring (0 to 20 mA)
4
Bipolar voltage input (-10 to +10 V )
0
MOP setpoint will not be stored
1
MOP setpoint will be stored in P1040
0
Reverse direction is allowed
1
Reverse direction inhibited
P0761 > 0
||
0 < P0758 < P0760
0 > P0758 > P0760
%
100 %
4000 h
ASPmax
P0760
P0758
P0757
P0759
P0761
P0757 = P0761
ASPmin
3 Functions
V
mA
x
10 V
100%
20 mA