Technical Data; Operating Conditions - Siemens SITRANS VP300 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SITRANS VP300:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Cleaning the enclosure
● Clean the outside of the enclosure and the display window using a cloth moistened with water or a mild detergent.
● Do not use aggressive cleaning agents or solvents. Plastic components or painted surfaces could be damaged.
The positioner is maintenance-free to a large extent.
Repair/Upgrading
Send defective devices to the repairs department, together with information on the malfunction and the cause of the
malfunction. When ordering replacement devices, please provide the serial number of the original device. You can find the
serial number on the nameplate.
Return procedure
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the
outside of the packaging. Any devices/replacement parts which are returned without a decontamination declaration will be
cleaned at your expense before further processing. For further details refer to the operating instructions.
See also
Return goods delivery note (http://www.siemens.com/processinstrumentation/returngoodsnote)
Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination)
Disposal

Technical data

Operating conditions

Ambient temperature
● Permissible ambient temperature for operation
Degree of protection
Mounting position
Vibration resistance
● Harmonic vibrations (sine) according to
DIN EN 60068-2-6/02/2008
● Bump (half-sine) according to DIN EN 60068-2-29/03.95
● Noise (controlled digitally) according to DIN EN 60068-2-
64/04/2008
Climate class
● Storage
● Transport
● Operation
1)
At ≤ -20 °C (-4 °F), the display refresh rate of the display is limited. At > 70 °C (158 °F), the contrast of the display is
1)
limited.
SITRANS VP300 (6DR63..)
A5E03359515-01, 03/2011
Devices identified by this symbol may not be disposed of in the municipal
waste disposal services under observance of the Directive 2002/96/EC on
waste electronic and electrical equipment (WEEE).
They can be returned to the supplier within the EC or to a locally approved
disposal service. Observe the specific regulations valid in your country.
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-40 ... +85 °C (-40 ... +185°F)
IP66 according to IEC EN 60529
Any, ventilation opening not upwards in wet environments
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis
100 m/s² (328 ft/s²), 27 ... 200 Hz, 3 cycles/axis
250 m/s² (820 ft/s²), 6 ms, 1000 shocks/axis
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz
According to DIN EN 60721-3-4
1K3
2K4
4K4, but -40 to +85 °C (-40 to +185 °F)