4. Confirm the selection with
The factory setting is "Linear <= 60 mm".
5. If required, set the tight closing function.
Use
or
to switch to the menu "1 Quick Start > 1.1 Autom. initialization > 1.1.2 Tight closing > Edit".
6. Select the tight closing function with
7. Confirm the selection with
8. Start the initialization by selecting the "Start" command and then "OK" in the menu "1 Quick Start > 1.1 Autom.
initialization > 1.2.3 Initialize".
The progress bar in the display indicates the initialization progress. Once the initialization process has been successfully
completed, the display will show the √ symbol.
9. Switch to the measurement view by pressing the
Result
Commissioning of the positioner is complete. The initialization settings are saved. After the initialization the positioner will
function with the new settings.
SITRANS VP300 (6DR63..)
A5E03359515-01, 03/2011
. The set actuator type is displayed.
or
. The set tight closing function is displayed. Factory setting is "Off".
button until the display shows the following: